1019 chars; verbs=true — Unit 3003 was inspected and found with a locked compressor. Locked-rotor amps were rated at 49, but the compressor pulled 63 amps with a hard-start kit and new
Job #9056
1019 chars; verbs=true — Unit 3003 was inspected and found with a locked compressor. Locked-rotor amps were rated at 49, but the compressor pulled 63 amps with a hard-start kit and new
0 photo signals (need 3 for service) [API proxy — warn only]
Fix: Attach at least 3 photos for this service job (before/after for coil cleaning / filter changes).
ServiceTitan API did not expose attachments; scored as warning until media endpoints are wired.
Refrigerant work indicated but no quantity logged (lb/oz + type)
Fix: Log freon/refrigerant type and amount (e.g. 'recovered 3 lbs R-410A').
Lead: Jose Vergara
No signature form/note signal [API proxy — warn only]
Fix: Collect customer signature on the job before marking complete.
Signature not API-confirmable yet; warning only until forms/attachments are wired.
Unit 3003 was inspected and found with a locked compressor. Locked-rotor amps were rated at 49, but the compressor pulled 63 amps with a hard-start kit and new capacitor installed. The compressor is not reliable and requires replacement. Due to the system being an older R-22 unit, a complete system changeout is recommended. The existing equipment is a 2.5-ton wall-mounted condenser and air handler. All parts used for troubleshooting were provided by Maintenance and were kept by Maintenance after testing. Unit 3003 was inspected and found with a locked compressor. Locked-rotor amps were rated at 49, but the compressor pulled 63 amps with a hard-start kit and new capacitor installed. The compressor is not reliable and requires replacement. Due to the system being an older R-22 unit, a complete system changeout is recommended. The existing equipment is a 2.5-ton wall-mounted condenser and air handler. All parts used for troubleshooting were provided by Maintenance and were kept by Maintenance after testing.