1972 chars; verbs=true — Inspect chiller, the temperatures on chillers is set at 44 and it's showing around 51. The QUINTA chiller was inspected and compressor A1 was found grounded and

FAIL

Photos

0 photo signals (need 2 for other) [API proxy — warn only]

Fix: Attach at least 2 photos for this other job (before/after for coil cleaning / filter changes).

ServiceTitan API did not expose attachments; scored as warning until media endpoints are wired.

PASS

Freon / refrigerant

Refrigerant quantity language found in notes

PASS

Lead tech closeout

Lead: Jose Vergara

FAIL

Customer signature

No signature form/note signal [API proxy — warn only]

Fix: Collect customer signature on the job before marking complete.

Signature not API-confirmable yet; warning only until forms/attachments are wired.

Closeout notes / invoice summary
Inspect chiller, the temperatures on chillers is set at 44 and it's showing around 51. The QUINTA chiller was inspected and compressor A1 was found grounded and will need to be replaced. Compressor A2 has a bad contactor that also requires replacement. Additional repairs include replacing the high-pressure cutout switch, suction and discharge transducers, and filter drier. A complete leak check will be performed, and the existing refrigerant will be recovered and properly disposed of. The system will then be charged with 18 pounds of new R-410A and tested. For the time being, the chiller will be operated using one compressor. Office to send quote. The QUINTA chiller was inspected and compressor A1 was found grounded and will need to be replaced. Compressor A2 has a bad contactor that also requires replacement. Additional repairs include replacing the high-pressure cutout switch, suction and discharge transducers, and filter drier. A complete leak check will be performed, and the existing refrigerant will be recovered and properly disposed of. The system will then be charged with 18 pounds of new R-410A and tested. For the time being, the chiller will be operated using one compressor. Chiller Inspection – Not Reaching Set Temperature Inspected the Quinta chiller after it was reported that the leaving-water temperature was approximately 51°F while set to 44°F. Compressor A1 was found grounded and requires replacement. Compressor A2 was found with a failed contactor that also requires replacement. Additional recommended repairs include replacement of the high-pressure cutout switch, suction and discharge transducers, and filter drier. A complete refrigerant leak check will be required. The existing refrigerant will be recovered and properly disposed of, and the system will be charged with 18 pounds of new R-410A and tested for proper operation. The chiller will temporarily operate on one compressor. The office will provide a repair proposal.