← All jobs

Job #9021

Mustang Station Apartments

Unit # 2-138 Bldg · 2500 Pepperwood Street, Farmers Branch, TX, 75234

Service HVAC- Residential · Juan Martinez · 9/2/2026, 5:00:50 PM

NOT DONEScore 40%
PASS

Notes quality

568 chars; verbs=true — Apt 2-138- Provide and install warranty compressor Recovered all freon from system then started on demo for compressor and filter dryer. Once removed used nitro

FAIL

Photos

0 photo signals (need 3 for service) [API proxy — warn only]

Fix: Attach at least 3 photos for this service job (before/after for coil cleaning / filter changes).

ServiceTitan API did not expose attachments; scored as warning until media endpoints are wired.

FAIL

Freon / refrigerant

Refrigerant work indicated but no quantity logged (lb/oz + type)

Fix: Log freon/refrigerant type and amount (e.g. 'recovered 3 lbs R-410A').

PASS

Lead tech closeout

Lead: Juan Martinez

FAIL

Customer signature

No signature form/note signal [API proxy — warn only]

Fix: Collect customer signature on the job before marking complete.

Signature not API-confirmable yet; warning only until forms/attachments are wired.

Closeout notes / invoice summary
Apt 2-138- Provide and install warranty compressor Recovered all freon from system then started on demo for compressor and filter dryer. Once removed used nitrogen and flush to clean out system to remove any oils or non condensables in system. Installed new compressor and filter dryer, pipe fitted together then brazed unit under nitrogen. Verified leak test at 350+psi. Once held pulled vaccum to sub 500 microns before charging system with 454b freon provided by impact. Verified system pressures and temperature before cleaning area and hauling away old equipment.